1. Introduksjon
This manual provides essential instructions for the safe installation, operation, and maintenance of your BEST LEDR-1 LED Emergency Light. Please read this manual thoroughly before installation and retain it for future reference. The LEDR-1 is designed to provide reliable emergency illumination during power outages, ensuring safety in commercial and residential environments.
2. Viktige sikkerhetsinstruksjoner
ADVARSEL: Fare for elektrisk støt. Koble fra strømmen før installasjon eller service.
- All service skal kun utføres av kvalifisert personell.
- Ikke monter i nærheten av gass- eller elektriske varmeovner.
- Ensure the electrical wiring is properly grounded.
- Do not use outdoors. This unit is designed for indoor use only.
- Ikke la strømledninger berøre varme overflater.
- Mount the unit in locations and at heights where it will not be subjected to tampering av uautorisert personell.
- Bruk av ekstrautstyr som ikke er anbefalt av produsenten kan forårsake en usikker tilstand.
- Ikke bruk dette utstyret til annet enn tiltenkt bruk.
- Allow battery to charge for a minimum of 24 hours after installation before testing.
3. Pakkens innhold
Kontroller at alle komponenter er til stede og uskadet når du åpner pakken:
- BEST LEDR-1 LED Emergency Light Fixture (1 unit)
- Monteringsutstyr (skruer, ankere)
- Wire Mutters
- Brukerhåndbok (dette dokumentet)
- AA NiCAD Battery (pre-installed or included separately)
4. Produktet er overview
The BEST LEDR-1 is a compact and efficient LED emergency light designed for wall-mount applications. It features a durable white thermoplastic housing and two adjustable LED lamp heads, providing 98 lumens of bright, white light (5000 Kelvin) during emergency situations. The unit operates on 120 Volts AC and includes a rechargeable NiCAD battery for backup power.

Figur 1: Foran view of the BEST LEDR-1 Emergency Light. This image shows the compact white thermoplastic housing with two adjustable LED lamp hoder.
Nøkkelfunksjoner:
- Bolig: White Thermoplastic
- Lyskilde: 2 LED heads
- Voltage: 120 volt vekselstrøm
- Batteri: NiCAD, 90 minutes average life
- Lyseffekt: 98 lumen
- Dimensjoner: Omtrent 14.75 cm L x 3.75 cm B x 3.75 cm H
5. Installasjon
The LEDR-1 is designed for flush wall mounting. Follow these steps for proper installation:
- Strømfrakobling: Before beginning any installation, ensure that the main power supply to the circuit where the emergency light will be installed is turned OFF at the circuit breaker or fuse box.
- Monteringssted: Select a suitable wall location for mounting. The unit should be mounted at a height and in a position that allows for optimal light distribution during an emergency. Ensure the mounting surface is solid and can support the fixture's weight.
- Klargjør monteringsoverflaten: Use the provided mounting hardware (screws and anchors) to secure the mounting plate or backplate of the emergency light to the wall. If the unit has a separate mounting plate, attach it first.
- Kablingstilkoblinger:
- Koble til svart ledning from the emergency light to the varm (strømførende) ledning from the building's electrical supply.
- Koble til hvit ledning from the emergency light to the nøytral ledning from the building's electrical supply.
- Koble til grønn ledning from the emergency light to the jordledning from the building's electrical supply.
- Use the provided wire nuts to secure all connections. Ensure all connections are tight and properly insulated.
- Batteritilkobling: If the battery is not pre-connected, connect the battery pack to the circuit board. Ensure correct polarity.
- Sikker armatur: Carefully tuck all wires into the junction box or fixture housing. Secure the emergency light fixture to the mounting plate or wall according to the specific design of the unit.
- Gjenopprett kraften: Once the installation is complete and all connections are secure, restore power to the circuit. The CHARGE INDICATOR light on the unit should illuminate, indicating that the battery is charging.
- Innledende kostnad: Allow the battery to charge for a minimum of 24 hours before performing the first test.
6. Drift
The BEST LEDR-1 Emergency Light operates automatically:
- Strøm på: When AC power is supplied to the unit, the charge indicator light will be ON, and the battery will be charging. The LED lamp heads will remain OFF.
- Power Outage: In the event of an AC power failure, the emergency light will automatically switch to battery backup mode, and the LED lamp heads will illuminate. The unit will provide emergency lighting for approximately 90 minutes.
- AC Power Restored: When AC power is restored, the LED lamp heads will turn OFF, and the unit will revert to charging the battery.
- Testknapp: A test button is located on the unit. Pressing this button simulates an AC power failure, allowing you to verify that the emergency lights function correctly. Release the button to return to normal operation.
- Justerbar Lamp Hoder: The two LED lamp heads can be manually adjusted to direct light to desired areas.
7. Vedlikehold
Regular maintenance ensures the longevity and reliability of your emergency light.
Batteritesting:
Perform the following tests according to local codes and regulations (typically monthly and annually):
- Månedlig test: Press and hold the test button for at least 30 seconds. The LED lamp heads should illuminate. Release the button; the lights should turn off, and the charge indicator should be ON.
- Annual Test: Disconnect AC power to the unit for a full 90 minutes. The LED lamp heads should remain illuminated for the entire duration. Reconnect AC power; the lights should turn off, and the charge indicator should be ON. If the unit fails to operate for the full 90 minutes, the battery may need replacement.
Rengjøring:
Clean the exterior of the unit and lamp heads periodically with a soft, damp klut. Ikke bruk skurende rengjøringsmidler eller løsemidler.
Batteribytte:
The NiCAD battery has a limited lifespan. If the unit fails the annual 90-minute test, the battery likely needs replacement. Contact a qualified electrician or the manufacturer for battery replacement instructions and compatible battery types.
8. Feilsøking
| Problem | Mulig årsak | Løsning |
|---|---|---|
| Emergency lights do not turn ON during power outage or when test button is pressed. |
|
|
| Charge indicator light is OFF when AC power is present. |
|
|
| Emergency lights do not stay ON for 90 minutes during annual test. |
|
|
9. Spesifikasjoner
| Trekk | Detalj |
|---|---|
| Modellnummer | LEDR-1 |
| Merke | BESTE |
| Husmateriale | White Thermoplastic |
| Lyskildetype | LED (2 heads) |
| Voltage | 120 volt vekselstrøm |
| Wattage | 2 watt |
| Lysstyrke | 98 lumen |
| Effektivitet | 49 lumen/watt |
| Fargetemperatur | 5000 Kelvin |
| Batteritype | NiCAD (1 AA battery required, included) |
| Average Battery Life (Emergency Mode) | 90 minutter |
| Installasjonstype | Innfelt veggfeste |
| Innendørs/utendørs bruk | Kun innendørs |
| Produktdimensjoner (L x B x H) | 14.75 cm x 3.75 cm x 3.75 cm |
| Varevekt | 0.01 unser |
| Kontrollmetode | Remote (Test Button) |
10. Garanti og støtte
The BEST LEDR-1 LED Emergency Light comes with a full manufacturer warranty. For specific warranty details, claims, or technical support, please refer to the warranty card included with your product or contact Best Lighting Products directly. Keep your purchase receipt as proof of purchase.
For assistance, please contact Best Lighting Products customer service.